ALL ALUMINIUM CONDUCTORS

ALL ALUMINIUM CONDUCTORS

PECIFICATION: BS 215, PART I,IEC 27, NIS 231

APPLICATION: FOR USE IN LOW VOLTAGE LINES, AND SOMETIMES ON LINES UP TO 66KV.RELAIVELY SHORH SPAN DISTRIBUTIONSCHEMES. AS FLEXIBLE BUSBAR CONNECTIONS IN HIGH VOLTAGE SUB-STATIONS.

NOTE: MAXIMUM PERMISSIBLE CONDUCTOR TEMPARATUREUNDER SERVICE CONDITIONS IS TAKEN AT 70O/C. MAXIMUM CURRENT RATING IN AIR IS CONSIDERED AT A TEMPERATURE OF 40O/C.

Product Description

Nominal cross sectional area
mm2
Conductor number x diameter of wire
mm
Nominal overall diameter
mm
Maximum Current rating A
------
in air
Weight kg/standard length

kg
Standard Delivery length

m
Delivery form
16
25
35
50
70
95
120
150
185
240
300
400
500
630
7 X 1.70
7 X 2.10
7 X 2.50
19 X 1.80
19 X 2.10
19 X 2.50
19 X 2.80
37 X 2.25
37 X 2.50
61 X 2.25
61 X 2.50
61 X 2.89
61 X 3.23
91 X 2.96
5.1
6.3
7.5
9.0
10.5
12.5
14.0
15.8
17.5
20.3
22.5
26.0
29.1
32.6
81
107
133
167
200
252
289
337
385
463
525
633
733
844
608
398
329
797
723
769
804
810
1500
1338
1652
1104
1379
1732
14,000
6,000
3,500
6,000
4,000
3,000
2,500
2,000
3,000
2,000
2,000
1,000
1,000
1,000
TWD 12
TWD 10
TWD 10
TWD 12
TWD 12
TWD 12
TWD 12
TWD 12
TWD 16
TWD 16
TWD 16
TWD 14
TWD 16
TWD 18
50 "ANT"
100 "BEETLE"
150 "HORNET"
7 X 3.10
19 X 2.67
19 X 3.25
9.3
13.4
16.3
167
259
337
867
877
866
6,000
3,000
2,000
TWD 12
TWD 12
TWD 12

Reviews